Montréal Combustion Logo
Technologies and equipment

Server Room Cooling: Requirements and Pitfalls in Montreal

Server room cooling for Quebec buildings: ASHRAE temperature range, comfort vs precision AC, Montreal winter pitfalls and how much redundancy to buy.

At a Glance

Server room cooling has to remove every watt the IT equipment draws, around the clock, all year — January included. Target ASHRAE's 18–27 °C range at the server inlets, use a dedicated unit rated for cold-weather operation, and size redundancy to what an hour of downtime actually costs.

Here is a number that surprises most property managers: a single rack drawing 5 kW puts out as much heat as ten 500 W baseboard heaters running non-stop — in a closed room, usually windowless, often in the core of an office floor. Server room cooling is not office air conditioning with a lower setpoint. It is a constant heat load that has to be removed in July and in January alike, with no evenings or weekends off.

That is where most problems start. The room was tied into the building’s system as an afterthought, or fitted with a wall-mounted unit picked for its BTU rating. It runs fine for three seasons. Then the first real cold snap arrives.

What is the right server room temperature?

Short answer: keep the air entering the equipment between 18 and 27 °C (64–81 °F), the recommended envelope in ASHRAE’s thermal guidelines for Classes A1 to A4, with a dew point between -9 and 15 °C. High-density Class H1 hardware calls for a tighter 18–22 °C band. Colder is not safer.

Three details make the difference in practice:

  • Measure at the server inlets, at the front of the racks, not at the thermostat by the door. A thermostat can read 21 °C while the top of a rack is pulling in 30 °C air.
  • Humidity matters as much as temperature. The 2021 (5th) edition of the ASHRAE guidelines allows up to 70% RH only where corrosive gases are low; without contamination testing, it suggests staying under 50%.
  • These ranges are recommendations, not regulations. The binding reference is your equipment manufacturer’s spec sheet and, if you have one, the service agreement with your IT team.

Server room cooling load: every watt becomes heat

Almost all the power IT equipment consumes ends up as heat. The math is simple in principle: add the actual IT draw (read at the PDUs or the UPS panel), the UPS’s own losses, lighting, and envelope gains — an exterior south wall, a ceiling under a flat roof. One ton of refrigeration is about 3.5 kW, or 12,000 BTU/h.

The classic mistake is adding up nameplate ratings. Those reflect the maximum the power supply can draw, rarely what it actually uses. The result is an oversized unit that short-cycles, dehumidifies poorly and wears out early. The opposite error is just as common: a load calculation done five years ago, before two storage racks moved in.

Comfort AC vs precision cooling

Comfort air conditioning is built for people: it pulls out a lot of moisture (latent heat) and runs a few hours a day in summer. A server room needs almost pure sensible cooling, without drying out the air, all year long.

Comfort AC (wall unit, building rooftop)Precision cooling (CRAC / dedicated unit)
Designed dutyIntermittent, summerContinuous, 24/7/365
Moisture removalHigh — can over-dry the airLow and controlled
Deep-cold operationOften limited or noneBuilt in from the start
Humidity controlRareIntegrated, tight tolerance
Upfront costLowHigher
Alarms and monitoringBasicAlarm contacts, BAS integration

For a 1–2 kW network closet, a well-chosen dedicated mini-split is still a sensible option. Beyond that, or as soon as an hour of downtime costs more than the price gap between the two, commercial precision air conditioning is the reasonable call.

Montreal winters: the pitfalls generic guides miss

Greater Montreal adds two constraints most online advice ignores.

Outdoor cold. A standard outdoor condenser loses head pressure once it drops below freezing: the compressor trips on low pressure, or the indoor coil ices up. The unit has to be designed for cold climates or fitted with low-ambient controls (condenser fan speed control, head pressure control) — and that belongs on the spec sheet, not in the salesperson’s pitch.

A building system that changes seasons. A room served by the building’s rooftop unit loses its cooling as soon as that unit switches to heating, or the BAS schedule shuts it down nights and weekends. The server room keeps no schedule.

Winter also offers an opportunity: cold outdoor air can cool for free through an air-side economizer or a glycol loop. That pays off in larger rooms, provided humidity is managed — January air is very dry once warmed, and overly dry air raises the risk of electrostatic discharge.

A Laval office building that only overheated in January

The property manager of an office building in Laval called us on a Monday in January: temperature alarms on the servers Friday night and Saturday. Everything had been fine the summer before. The 4 kW room was cooled by a mini-split added during a fit-out, with its condenser on the flat roof.

On site, the indoor unit showed a low-pressure fault. The condenser had no low-ambient control; at -20 °C, the compressor tripped within minutes. On weekdays, a door left ajar and the corridor heating masked the problem. On weekends, the door stayed shut. A data logger left in place for ten days showed rack inlet air climbing above 32 °C every cold night.

The fix: a dedicated unit rated for cold-weather operation, an inlet temperature sensor at the front of the racks tied into the BAS with text alerts, and the existing mini-split kept as backup. The cost of the downtime avoided was never calculated — but the manager stopped getting Sunday phone calls.

How much redundancy is worth paying for?

This is a financial question before it is a technical one: what does an hour of server downtime cost you? If the answer is “not much,” one well-maintained unit and an alarm will do. If it runs to thousands of dollars, you are looking at N+1 redundancy — one more unit than the load requires, able to carry it alone.

In between, several measures cost very little:

  • an inlet temperature alarm that reports outside the building;
  • a dedicated electrical circuit for the cooling unit, on the generator if the IT load is;
  • a maintenance contract with at least one pre-winter visit to check low-ambient controls and the condensate drain;
  • a written emergency plan: who to call, which equipment to shut down first if the temperature climbs. Our 24/7 emergency repair team handles these units around the clock.

Quebec rules and funding

Quebec’s Regulation respecting halocarbons prohibits releasing refrigerant to the atmosphere and governs how it is handled: any work on the refrigerant circuit, including recharging, must be done by a qualified contractor. A unit that “loses” refrigerant every year has a leak to find and fix; topping it up at each visit is neither a repair nor a defensible practice. Our glossary entry on refrigerant covers the basics.

On the funding side, Hydro-Québec’s Efficient Solutions program supports businesses that improve the energy efficiency of commercial, institutional or industrial buildings, heat recovery included. A server room produces exactly the kind of steady waste heat that can preheat outdoor air or water; check eligible measures in the program’s calculation tool before signing off on the project.

Before your next meeting with IT

Ask for three numbers: the actual power drawn in the room (in kW, read at the UPS), the rack inlet temperature on the last very cold morning, and the estimated cost of one hour of downtime. With those three figures, choosing between a dedicated mini-split, a precision unit and N+1 redundancy stops being a matter of opinion.

The server room is often the smallest space in the building and the only one that never sleeps. Treating it like an ordinary office is the most expensive saving a property manager can make.

Frequently Asked Questions

What temperature should a server room be kept at?
ASHRAE's thermal guidelines recommend 18 to 27 °C (64 to 81 °F), measured at the air inlet of the equipment rather than at a wall thermostat. For high-density Class H1 hardware, the recommended band narrows to 18 to 22 °C. Running colder than needed does not add reliability; it mostly adds energy cost.
Can I use a regular ductless mini-split to cool a server room?
For a small, lightly loaded network closet, a dedicated mini-split can work, provided it is rated or fitted for low-ambient winter operation and sized to the measured load. Comfort units remove a lot of moisture and are not designed for continuous year-round duty, so above a few kilowatts, or when downtime is expensive, precision cooling is the safer choice.
How many BTUs or tons of cooling does a server room need?
Nearly all the electricity used by IT equipment becomes heat, so 1 kW of IT load needs roughly 1 kW of cooling, plus the UPS losses, lighting and heat gains through walls and roof. One ton of refrigeration is about 3.5 kW, or 12,000 BTU/h. Start from the power measured at the PDUs or UPS, not from nameplate ratings.
Why does my server room AC stop working in winter?
Many building systems switch to heating or shut down in winter, while a server room produces heat all year. An outdoor condenser without low-ambient controls loses head pressure in deep cold and trips on its safeties. The fix is a unit designed for Quebec winters or a cooling source independent of the heating plant.

Sources

  1. New ASHRAE guidelines challenge efficiency drive — Uptime Institute , October 21, 2021
  2. Data center temperature and humidity guidelines — TechTarget , February 10, 2025
  3. Solutions efficaces : Appuis financiers pour les entreprises — Hydro-Québec

24/7 Emergency — Fast Response Across Grand Montréal

Boiler failure, air conditioning down in a heat wave, or equipment breakdown? Our technicians respond quickly, summer and winter.

450-473-0909