Iced-Up Commercial Heat Pump — When Defrost Fails to Clear It
In heating mode, a heat pump extracts heat from outdoor air: its outdoor coil therefore runs colder than the surrounding air, and moisture deposits on it as frost. That is expected behaviour, and the unit clears it on its own through a periodic defrost cycle. The trouble starts when the ice stops going away: heat transfer collapses, backup heat takes over and the energy bill climbs — sometimes for weeks before anyone notices.
Why does the defrost cycle no longer clear the ice?
Defrost is a commanded sequence: the heat pump temporarily reverses its cycle to warm the outdoor coil, usually with the outdoor fan stopped during the operation. Three families of faults disrupt that sequence. Control: a failing defrost board or timer, or a temperature sensor that is misplaced, detached from the coil or out of calibration — the controller believes the coil is clear when it is not. Reversal: a four-way reversing valve that does not shift fully keeps the coil from warming up. Capacity: a low refrigerant charge, often the sign of a leak, or a fouled coil reduce heat exchange to the point where defrost ends without melting everything. On top of these comes a very Québec-specific constraint: defrost water that cannot drain and refreezes at the bottom of the unit because of blocked drainage, insufficient clearance or snow piled around the equipment.
What can you safely check?
Without opening the unit or touching the refrigerant circuit: clear snow and ice around the unit and free the air inlets and outlets, keeping a safe distance from the fins; watch a full sequence to note whether a defrost triggers at all and how long it lasts; record any code or indicator light shown at the controller to relay to the technician; and check how the backup heat behaves — running continuously confirms the loss of capacity. Never spray hot water on the coil, never chip at the ice and never force a fan that is frozen in place. Preventive maintenance scheduled before winter — coil cleaning, sensor and drainage checks — prevents most of these situations.
When should you call a technician?
As soon as the ice persists after a full clearing, the coil stays encased over several cycles, the outdoor fan is locked by ice, or backup heat runs non-stop. Checking a defrost sensor, a reversing valve or a refrigerant charge requires measurements and safe access — often on a roof. Montréal Combustion diagnoses and restores commercial heat pumps across Greater Montréal, the North Shore and the South Shore in a B2B setting: defrost sequence checks, refrigerant measurements, drainage and clearance corrections. 450-473-0909.