Montréal Combustion Logo
Diagnostics & Troubleshooting

Burner won't light after summer shutdown: a fall restart tree

Gas burner won't light after sitting all summer? A fall start-up troubleshooting tree built on what you see at the sight glass, before the cold sets in.

At a Glance

When a burner won't light after summer shutdown, a worn part is rarely the cause. It's usually something the summer changed around it: a disabled call for heat, low water, a closed valve, a gas line full of air, an oxidized flame rod. Sorting what you see during trial for ignition into four cases finds the cause in one visit instead of a parts order.

Every fall, someone in a boiler room says it: “It ran fine in April, it’ll fire right up.” That assumption costs more service calls than any worn part. When a burner won’t light after summer shutdown, the burner itself is usually fine. What stops it is everything five months of downtime changed around it: a controller left in summer mode, a valve closed for renovations, rerouted gas piping, a flame rod that spent the summer in a damp basement.

This guide is for technicians doing October and November start-ups across Greater Montréal. It skips the theory of the start-up sequence and starts from what you actually see through the sight glass, then ties each observation to the causes specific to a seasonal restart.

Why is a burner that won’t light after summer a different problem?

Short answer: a fall no-start is almost always a condition, not a component. While the plant sat idle, things around the burner changed: settings, renovations, water level, insects, humidity. On the first call for heat, the flame safeguard either won’t start the sequence or locks out. The method: watch the ignition trial, classify the symptom, and check what changed since spring first.

That shift matters on site. A January lockout points toward wear. The same lockout in October starts with a question for the superintendent or property manager: what work was done in this building over the summer? A renovated kitchen, a repainted mechanical room, a drained loop, a replaced controller — any of them can disable a burner without anyone touching it.

🧰 Tools you’ll need Multimeter (volts and microamps), digital manometer for gas pressure, combustion analyzer, inspection light and mirror, fine emery cloth for the flame rod, locks and tags, and the flame safeguard manufacturer’s manual — it sets the trial-for-ignition timing and the minimum flame signal.

⚠ Safety Every failed ignition trial puts gas into the combustion chamber. Don’t keep resetting “to see what happens,” never jumper a pressure switch or limit, and never purge a gas line into the boiler room. In Québec, gas work is done by a contractor holding the appropriate RBQ licence, under CSA B149.1 as adopted in the Gas chapter of the Construction Code.

Watch first, reset later: the four-case grid

Before you touch the reset button, read the fault code and watch one complete trial through the sight glass. What you observe places the problem in one of four branches of the burner’s sequence of operations:

What you seeBranchTypical fall start-up suspects
Nothing moves, no blower1. Call for heatSummer mode, warm weather shutdown, BMS schedule, low water
Blower runs, no spark2. Air provingNest in the intake, water in switch tubing, seized damper
Spark visible, no flame3. GasClosed valve, air in the line, unpowered gas valve
Brief flame, then lockout4. Flame provingOxidized rod, dusty scanner lens, poor ground

If the boiler ran for a few days before it started locking out over and over, you’re in different territory: recurring lockouts, where the root cause usually hides in load or draft.

Case 1 — The burner never gets a call

The first fall trap is hunting for a burner fault when nothing is asking the burner to run. On outdoor reset controllers, warm weather shutdown disables the boiler above a set outdoor temperature, and one mild October afternoon is enough to keep it off. Also check the controller’s summer mode, the building automation schedule, the service switch and the temperature limits.

Then check the water. If the loop was drained or repaired over the summer, the low-water cutoff may still be open or waiting for a manual reset. The burner gets no call until that contact closes, and that’s by design: a boiler without water must never fire.

Case 2 — The blower runs, but the ignition trial never comes

The safeguard has the call, the blower starts, then nothing. It’s waiting for air proving that never arrives, or for an interlock that stays open. After a summer off, the usual culprits are small: a wasp or bird nest in the intake or vent, condensate sitting in the pressure switch tubing, a seized motorized damper whose end switch no longer makes.

On commercial burners, the interlock string also includes high and low gas pressure switches and the valve proof-of-closure switch. A low gas pressure switch that tripped during a summer gas shutdown may need a manual reset; controls distributor Stromquist notes that these start-up interlocks hold off ignition until they close.

Case 3 — Spark, but no flame

You see or hear the spark, but no flame appears during the trial window, which only lasts a few seconds. Beckett, for example, specifies a 4-second flame establishing period on its CG series commercial gas burners. When no flame is visible, the manufacturer points to the gas supply and gas train, the air settings, then the ignition system.

In the fall, the check order is straightforward:

  1. Manual valves. Closed for the summer or during renovations, they’re the most mundane cause and the most often missed.
  2. Voltage at the gas valve coil during the trial. No voltage means the problem is upstream, in the control; voltage but no opening means the valve.
  3. Manifold pressure during the trial, on a digital manometer, against the rating plate. Good static pressure proves nothing.
  4. Air in the line. If a plumber added an appliance or rerouted piping this summer, the section feeding the boiler may be full of air. Purging follows CSA B149.1, done by a licensed contractor who vents the mixture safely.

Case 4 — Flame lights, then the safeguard locks out

You see flame through the sight glass, then the control shuts the gas at the end of the trial. The burner is working; the proof is missing. The flame detector — ionization rod or optical scanner — isn’t sending the control a strong enough signal.

After a summer in a damp basement boiler room, sometimes dusty from renovations, the causes are predictable: an oxidized flame rod, a UV scanner lens filmed with dust, a corroded ground between the burner head and the control. Measure the flame signal during the trial, clean, tighten the ground, measure again and compare against the manufacturer’s threshold. If the signal stays weak with a good flame, look at the detector or the amplifier.

Longueuil: the kitchen reno that emptied the gas line

Late October, an office building in Longueuil calls: the lead boiler locks out on every attempt, and the lag boiler hasn’t been called yet. On site, the blower starts, pre-purge runs, the spark is strong. No flame. The fault code reads ignition failure.

The manual valves were open and the gas valve was getting voltage. The manometer at the manifold showed low, unstable pressure during the trial. A few questions to the property manager turned up the cause: in July, a caterer had a new range connected to a branch of the same line. The section feeding the boiler room was isolated during the work, then reopened without being purged.

The licensed gas fitter purged the line to code, venting outdoors. The burner lit on the first try. We ran three full cycles, a combustion analysis, and checked pressure under load with the kitchen running. No parts were replaced. The report recommended that any change to the gas piping be flagged to the contractor responsible for the boiler room.

What Québec’s calendar and code add

Around Montréal, the first freezing nights usually arrive between mid-October and early November. So restarts often happen in a rush on a cold morning, when they could have been a planned test a few weeks earlier. Basement boiler rooms that stay humid all summer speed up oxidation on flame rods and contacts.

On the regulatory side, the Gas chapter of Québec’s Construction Code incorporates CSA B149.1, which covers line purging, piping changes and adding appliances. A well-documented fall restart fits naturally into a gas heating and combustion service program.

Before the first −10 °C night: book a cold-start test

Don’t let the first real call for heat be the test. Schedule a start-up with a technician on site for every boiler while it’s still mild: call for heat, air proving, pressure under load, flame signal and combustion analysis, all logged. Ask the property manager for a list of summer work before heading down to the boiler room.

For the manager, that planned start-up trades an emergency call for a daytime visit, and a cold building for a report on file. It’s exactly the kind of job Montréal Combustion would rather do in October than at 6 a.m. in January.

Frequently Asked Questions

Why won't my boiler light after being off all summer?
Usually nothing broke. Something around the boiler changed while it sat: the controller is still in summer mode or warm weather shutdown, a manual gas valve was closed, low water is holding the low-water cutoff open, or the gas piping was modified during renovations. An oxidized flame rod or an air intake blocked by a nest round out the list. A qualified technician checks these in the order of the start-up sequence.
How many times should you reset a burner that won't ignite?
As few as possible. Every failed trial for ignition puts gas into the combustion chamber, and the flame safeguard locks out precisely to stop it from building up. Read the fault code and note which step the start-up stopped at before resetting; if it locks out again, stop and call a gas technician.
Should a commercial boiler be checked before turning the heat back on in the fall?
Yes, ideally before the first freezing nights. A scheduled start-up with a technician on site verifies the call for heat, air proving, gas pressure under load and flame signal while the weather is still mild. Finding the same fault on a -15 °C morning means an emergency call and a building that's losing heat.
Can air in the gas line stop a burner from lighting?
Yes. After piping work, or when a section has been isolated for a long time, the line can hold air instead of gas. The burner then tries to light a mixture that won't ignite and locks out. In Québec, purging gas piping is governed by CSA B149.1 and must be done by a properly licensed contractor who vents the mixture safely.

Sources

  1. Troubleshooting Common Honeywell 7800 Series Lockouts — Stromquist & Company , August 1, 2025
  2. Troubleshooting Guides — Beckett Corporation
  3. Chapitre Gaz du Code de construction — Régie du bâtiment du Québec
  4. CSA B149.1 – Code d'installation du gaz naturel et du propane — Régie du bâtiment du Québec

24/7 Emergency — Fast Response Across Grand Montréal

Boiler failure, air conditioning down in a heat wave, or equipment breakdown? Our technicians respond quickly, summer and winter.

450-473-0909